| Features Provided | high inrush protection |
| Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 10000.0 ac all locations |
| Reset Method | manual |
| Pole Quantity | 3 |
| Circuit Protection Type | overcurrent all locations |
| Manual Actuator Type And Quantity | 1 toggle |
| Trip Release Ambient Temp Rating | 40.0 deg celsius nominal all locations |
| Mounting Facility Type And Quantity | 3 slot and 3 unthreaded hole |
| Mounting Slot Width | 0.562 inches nominal |
| Actuator Function | trip-reset |
| Unthreaded Mounting Hole Diameter | 0.234 inches nominal |
| Operating Voltage Type And Rating Per Pole In Volts | 240.0 ac all locations |
| Body Length | 3.000 inches nominal |
| Trip Release Method | thermal-magnetic all locations |
| Actuator Position Designation | at pole two |
| Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 140.0 all locations |
| Main Contact Tripping Mechanism Type | trip free |
| Case Material | plastic |
| Inclosure Protection Type For Which Designed | general purpose |
| Boss Height | 0.187 inches nominal |
| Trip Release Characteristic | instantaneous all locations and time delay all locations |
| Frequency In Hertz | 60.0 all locations |
| Terminal Type And Quantity | 3 clip and 3 compression |
| Body Width | 3.000 inches maximum |
| Center To Center Distance Between Terminals Parallel To Width | 1.000 inches nominal |
| Body Style | multipole-single actuator type |
| Trip Delay Time In Seconds Per Rated Continuous Current | 35.000 minimum at 200 pct all locations and 100.000 maximum at 200 pct all locations |
| Body Height | 2.375 inches nominal |
| Maximum Continuous Load Current Rating Per Pole | 60.0 amperes ac all locations |
| Storage Type | general purpose warehouse |