Thread Quantity Per Inch | 32 |
Thread Series Designator | unc |
Center To Center Distance Between Terminals Parallel To Length | 1.938 inches nominal |
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 2000.0 ac single location |
Reset Method | manual |
Circuit Protection Type | overcurrent single location |
Pole Quantity | 1 |
Manual Actuator Type And Quantity | 1 toggle |
Mounting Facility Type And Quantity | 2 threaded hole |
Actuator Function | trip-reset |
Operating Voltage Type And Rating Per Pole In Volts | 115.0 ac single location |
Body Length | 2.500 inches nominal |
Fragility Factor | moderately rugged |
Actuator Position Designation | at pole one |
Trip Release Method | magnetic-hydraulic single location |
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 |
Case Material | plastic |
Main Contact Tripping Mechanism Type | trip free |
Inclosure Protection Type For Which Designed | dustproof and fungus proof |
Boss Height | 0.140 inches nominal |
Trip Release Characteristic | time delay single location |
Frequency In Hertz | 60.0 |
Terminal Type And Quantity | 2 threaded stud |
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.062 inches nominal |
Nominal Thread Size | 0.138 inches |
Mounting Surface To Terminal End Distance | 2.471 inches nominal |
Body Width | 0.750 inches nominal |
Special Handling Feature | magnetic |
Body Style | 12a single pole type |
Trip Delay Time In Seconds Per Rated Continuous Current | 4.000 minimum at 200 pct and 10.000 maximum at 200 pct single location |
Arc Quenching Method | magnetic blowout |
Maximum Continuous Load Current Rating Per Pole | 8.0 amperes ac single location |
Storage Type | general purpose warehouse |
Internal Trip Release Configuration | series trip single location |